30kVA 208/220V 3-Phase Wye Online UPS Extended Runtime, ULT-P30KL33LV

Out of stock
SKU
ULT-P30KL33LV
$15,199.00

Capacity: 30000VA / 30000W (30kVA / 30kW)
Topology: Online double-conversion
Wave Form: Sine wave
Voltage & Configuration: 120/208V or 127/220V 3-phase Wye

Features:
• DSP-controlled technology
• Active power factor correction in all phases
• 1.0 power factor
• High overload threshold
• ECO Mode & EPO function
• 50/60Hz frequency converter
• Built-in MBS
• Expandable battery runtime
• Option to parallel up to 3 units

The UltimaPro 33 is a 3-phase Wye double-conversion online UPS using PWM transformer-less technology, DSP-controlled technology, APFC in all phases, and ATS function for a high performing, reliable UPS for comprehensive power protection, performance, and efficiency. Enhanced features such as APFC, MBS, dual input power sources, and parallel-redundancy flexibility offers even greater reliance in power source and seamless operation. The APFC feature monitors input voltage for leading or lagging to correct as needed to ensure all phases are balanced to maintain high power efficiency and prevent harmonic currents from distortion so mission-critical equipment, especially sensitive equipment, receive higher quality power for optimal equipment performance. Customizable features such as adjustable charging current, frequency converter, ECO Mode, and others make this the ideal solution for organizations demanding the highest level of power quality and reliability.

 

Protects From
Brief blackouts
Power sag
Power surge

Undervoltage
Overvoltage
Line noise

Frequency variation
Switching transient
Harmonic distortion

 

Typical Applications
Server rooms
Surveillance center

IT closets
Networking equipment

Telecom equipment
Light industrial location

 

Main Features
True Online Double-Conversion Topology
True online double-conversion topology for zero transfer time from Line Mode to Battery Mode in case of a power disturbance prevents malfunction of mission-critical equipment.

High Overload Threshold Threshold
Keeps the UPS running in Line Mode when overloaded for a period time. This series will keep running in Line Mode up to 60 minutes at 110% overload capacity and up to 1 minute at 130% overload capacity.

DSP Controlled Technology
DSP (digital signal processor) controlled technology for high reliability, accuracy, and efficiency.

APFC in all Phases
APFC (active power factor correction) improves the power factor and power quality by reducing the load on the electrical system while improving energy efficiency and reducing power loss. By having APFC in all phases, the UPS is able to deliver reliable power protection.

Compact Design
Space-saving design with high performance capabilities with flexibility to expand in size as business needs increase.

Maintenance Bypass Switch (MBS)
Safely service the UPS while keeping connected equipment powered for zero downtime with the built-in MBS.

8A to 24A Adjustable Battery Charger
Select the battery charger up to 24A based on the number of external battery banks connected to the UPS for faster recharge times.

EMI / RFI Filter
EMI / RFI filter suppresses electromagnetic noise and radio frequency interference transmitted from AC power.

Emergency Power Off (EPO) Tab
Instantly shut off the UPS and prevent the UPS from supplying power in the event of an emergency.

Dual Input
Hardwire the primary input power with Mains Input and secondary power source to Bypass Input for redundant power supply. If connected to an ATS, the Main Input will switch over to battery power while the secondary power source starts up if the Mains Input power fails or UPS is damaged. Once the secondary power source (usually generator) starts up to power the UPS, the UPS will run on generator power until the main power supply returns. If for some reason the secondary power does not start up, connected equipment will continue to run on battery power.

NOTE: Requires ATS (automatic transfer switch) for the UPS to automatically switch between the two input power sources.

Expandable Battery Runtime
Add up to 3 external battery banks to extend the battery runtime of your UPS.

N+X or N Parallel Option (up to 3 Units)
N+X Parallel Redundancy (up to three units)
This series allows for the expansion of the UPS reliance with a parallel-redundant setup up to 3 units (N+X) or a parallel-capacity system (N) to increase overall capacity up to 3 units for 90kVA capacity.

Advanced Battery Management
Maximize battery performance and lifespan with an intelligent, 3-stage battery charging system to auto-sense the optimal battery charging performance based on battery levels. Charging will be either constant current, constant voltage, or floating for optimal battery performance.

Cold Start Capable
Turn on the UPS even without utility power as long as there is sufficient battery power.

4.3-inch Touchscreen LCD
Large, easy-to-read LCD screen shows real-time status information of your UPS power conditions including the voltages, capacity level, battery level, faults, event logs, settings, and more.

Intelligent Slot
For use with a network management card to remotely monitor and control the UPS from a web browser.

Power Management Software
Monitor and control the UPS from your computer with the included user-friendly software to automate computer shutdown, monitor battery levels, set UPS parameters, receive alerts of abnormalities, and more.

Optional Accessories (Not Included)
• External Battery Bank - See model # ULT-P30K33LVEB for compatibility with this UPS.
• Network Management Card - For remote power monitoring. See model number #SNMP3-2 for compatibility with this UPS series.
• Parallel Cable - Parallel up to 3 units for parallel redundancy. 1 x parallel cable required per UPS set.

Warranty
1-year equipment warranty and 1-year battery warranty. See Terms and Conditions, and Warranty Policy pages for additional information.



WARNING: The batteries, battery posts, terminals, and related accessories can expose you to chemicals including lead and lead compounds, which are known to the State of California to cause cancer and birth defects, or other reproductive harm. Wash hands after handling. For more information, go to www.p65warnings.ca.gov.
OVERVIEW
Model ULT-P30KL33LV
Capacity 30kVA / 30kW (30000VA / 30000W)
Phase 3-phase in / 3-phase out
Topology Online double-conversion
INPUT
Voltage & Configuration 3 x 120/208Vac Wye (3Ph + N + G) 3 x 127/220Vac Wye (3Ph + N + G)
Voltage Range 138 - 270Vac at 50% load
173 - 253Vac at 100% load
Frequency (Synchronized Range) 50 / 60Hz +/- 4Hz
Frequency (Battery Mode) 50 / 60Hz +/- 1Hz
Power Factor >0.99 at 100% load
THDi <3% at linear load / <5% at non-linear load
Inlet Hardwire terminal
OUTPUT
Voltage & Configuration 3 x 120/208Vac Wye (3Ph + N + G) 3 x 127/220Vac Wye (3Ph + N + G)
Frequency Range
(Synchronized Range)
50Hz: 46 - 54Hz
60Hz: 56 - 64Hz
Frequency Range (Battery Mode) 50 / 60Hz +/- 0.1Hz
Voltage Regulation <1%
Voltage Balance  
Current Crest Ratio 3:1 (max.)
THDv for Linear-Load <2% at linear load
<4% at non-linear load
Transient Reponse  
Transient Recovery Time  
Phase Displacement  
Power Factor 1.0
Overload Threshold Line Mode: 110%: up to 60 minutes; 125%: up to 10 minutes; 150%: up to 1 minute; >150%: immediate shutdown
Battery Mode: 110%: up to 30 seconds; 130%: up to 10 seconds; >130%: up to 1 second
Wave Form (Battery Mode) Sine wave
Outlet Hardwire terminal
TRANSFER TIME
Line To/From Battery 0ms
Inverter To/From Bypass 0ms
(<4ms interruption from inverter to bypass if phase lock fails)
EFFICIENCY
Line Mode 93% at full load with batteries fully charged
Battery Mode  92.5%
ECO Mode 97% at full load with batteries fully charged
BATTERY
Quantity & Size This is an extended runtime model, no batteries are inside. Must purchase separate external battery bank, model # ULT-P30K33LVEB, and batteries.
Charging Current 8A to 24A (adjustable)
PROTECTION
Emergency Power Off (EPO) Yes
Overload Protection Yes
Overcharge Protection Yes
Surge Suppression Yes
EMI / RFI Filter Yes, full time
ADDITIONAL FEATURES
MBS Yes, built-in maintenance bypass switch to safely route electricity during maintenance and servicing
Parallel Option Yes, requires 1 x parallel cable and parallel card per UPS (not included)
Parallel Units Yes, up to 3 units can be set up in parallel
ECO Mode Yes
COMMUNICATION
USB Port Yes, for power management software to control and monitor the UPS conditions
RS232 Port Yes, for firmware updates only
Software Compatible with Windows 10/8/7, Server 2012 R2 / 2008 R2, Linux 32-Bit / 64-Bit, Sun Solaris, IBM Aix, Compaq True64, SGIIRIX, FreeBSD, HP-UX, mac
Intelligent Slot Yes, for SNMP3-2 card (not included) for remote power management
STATUS INDICATORS
LCD Screen Yes, 4.3-inch touchscreen shows Input/Output Voltages, Battery Level, Load Level, Fault, status codes, event logs, settings, and more
Audible Alert Yes
WARRANTY
Warranty 1-Year: Equipment and Battery Warranty. See the Terms & Conditions, and Warranty Policy pages for additional information.
ENVIRONMENT
Installation Location For indoor, temperature-controlled location free of contaminants only
Cooling Built-in fan
Operating Temperature 0°C up to +40°C / +32°F up to +104°F
Operating Humidity <95% non-condensing
Noise <60dB at 1 meter
Operating Altitude <1000 meters
(Note: Output power derates at 1% per 100 meters when installed or used in locations with altitude above 1000 meter)
PHYSICAL
Color Black
Form Factor Tower
Product Dimensions (DWH) 790 x 420 x 1200 mm / 31.1 x 16.5 x 47.2 in
Product Weight 150 kg / 330.8 lb

 

Product specifications are subject to change without further notice. Maruson assumes no responsibility, and disclaims all liability, for any damages that may result from the use of this information or for any errors or omissions. Battery backup time varies with equipment, configuration, battery age, temperature, etc.

Optional Accessories (Not Included):
ULT-P30KLVEB -External battery bank for ULT-P30KL33LV
SNMP3-2 - Remote power management card for UltimaPro 33 series
Parallel Kit - Set up to three units in parallel configuration. Requires one cable to and from each UPS in parallel.
ATS (automatic transfer switch) - Auto transfer power source from Mains Input to Bypass Input if Mains Input fails

Brochure
Download here.

User Manual
Download here.

Software
Download here.

You must connect the USB from your UPS to your computer to use the software.

Compatible Operating Systems
Windows OS: Windows 10/ Windows 8/ Windows 7/ Windows Server 2016/ Windows Server 2012/ Windows Server 2012 R2/ Windows Server 2008/ Windows Server 2008 R2
mac OS: Mac OS 10.6/ 10.7/ 10.8/ 10.9/ 10.10/ 10.11
Linux 32-Bit and 64-Bit: Fedora 7/Redhat Enterprise 7.5/Centos 7/Open SUSE 11.4/Debian 7/Ubuntu 18.10
Virtual Machines (Agent and Client): VMware ESX/ESXi 6.5

LET'S CHAT

Not sure which model to purchase? Or, need help with a purchased item? Let us know how we can help.

PRODUCT REGISTRATION

Register your product for warranty coverage and expediated service requests.

WARRANTY

Find additional information on our warranty policy.