20kVA 360/380/400/415V 3-Phase Wye Online UPS, ULT-P20K33HV

Out of stock
SKU
ULT-P20K33HV
$0.00
( Contact Sales )

Capacity: 20000VA / 20000W (20kVA / 20kW)
Topology: Online double-conversion
Wave Form: Sine wave
Voltage & Configuration: 208/360V, 220/380V, 230/400Vac, or 240/415V 3-phase Wye

Features:
• DSP-controlled technology
• Active power factor correction in all phases
• 1.0 power factor
• High overload threshold
• ECO Mode & EPO function
• 50/60Hz frequency converter
• Built-in MBS
• Option to parallel up to 6 units
• Option to add an isolation transformer

The UltimaPro 33 is a 3-phase double-conversion online UPS using PWM transformer-less technology, DSP-controlled technology, APFC in all phases, and ATS function for a high performing, reliable UPS for comprehensive power protection, performance, and efficiency. Enhanced features such as APFC, MBS, dual input power sources, and parallel-redundancy flexibility offers even greater reliance in power source and seamless operation. The APFC feature monitors input voltage for leading or lagging to correct as needed to ensure all phases are balanced to maintain high power efficiency and prevent harmonic currents from distortion so mission-critical equipment, especially sensitive equipment, receive higher quality power for optimal equipment performance. Customizable features such as adjustable charging current, frequency converter, ECO Mode, and others make this the ideal solution for organizations demanding the highest level of power quality and reliability.

 

Protects From
Brief blackouts
Power sag
Power surge

Undervoltage
Overvoltage
Line noise

Frequency variation
Switching transient
Harmonic distortion

 

Typical Applications
Server rooms
Surveillance center

IT closets
Networking equipment

Telecom equipment
Light industrial location

 

Main Features
True Online Double-Conversion Topology
True online double-conversion topology for constant, clean power supply for connected equipment with output power isolated from common input power quality issues. Zero transfer time ensures seamless, uninterrupted operation when a power disruption occurs.

High Overload Threshold Threshold
Keeps the UPS running in Line Mode when overloaded for a period time. This series will keep running in Line Mode up to 60 minutes at 110% overload capacity and up to 1 minute at 130% overload capacity.

DSP Controlled Technology
DSP (digital signal processor) controlled technology for high reliability, accuracy, and efficiency.

APFC in all Phases
APFC (active power factor correction) improves the power factor and power quality by reducing the load on the electrical system while improving energy efficiency and reducing power loss. By having APFC in all phases, the UPS is able to deliver reliable power protection.

Maintenance Bypass Switch (MBS)
Safely service the UPS while keeping connected equipment powered for zero downtime with the built-in MBS.

1A to 12A Adjustable Battery Charger
Adjust the battery charger based on the number of batteries in the UPS for faster recharge times.

EMI / RFI Filter
EMI / RFI filter suppresses electromagnetic noise and radio frequency interference transmitted from AC power.

Emergency Power Off (EPO) Tab
Instantly shut off the UPS and prevent the UPS from supplying power in the event of an emergency.

Dual Input
Hardwire the primary input power with Mains Input and secondary power source to Bypass Input for redundant power supply. If connected to an ATS, the Main Input will switch over to battery power while the secondary power source starts up if the Mains Input power fails or UPS is damaged. Once the secondary power source (usually generator) starts up to power the UPS, the UPS will run on generator power until the main power supply returns. If for some reason the secondary power does not start up, connected equipment will continue to run on battery power.

NOTE: Requires ATS (automatic transfer switch) for the UPS to automatically switch between the two input power sources.

Transformerless Design
Transformer-free design uses advanced electronic components to perform power conversion, voltage regulation, and power conditioning instead of a transformer. Some of the advantages include high efficiency (particularly at lower loads), lower noise level, reduced heat generation, improved reliability, reduced harmonic distortion, smaller footprint and weight, enhanced scalability, and lower total cost of ownership.

Generator Compatible
This UPS is compatible with inverter generators using electronic governors. Inverter generators produce pure sine wave for better performance and "cleaner" power. Electronic governors uses an electronic control system that detects changes in the load and can adjust the throttle to control the engine and generator control functions for output power that is reliable and constant under variable loads.

Compact Design
Space-saving design with high performance capabilities with flexibility to expand in size as business needs increase.

N+X or N Parallel Option (up to 6)
This series allows for the expansion of the UPS reliance with a parallel-redundant setup up to 6 units (N+X) or a parallel-capacity system (N) to increase overall capacity.

Smart Battery Management
Maximize battery performance and lifespan with an intelligent, 3-stage battery charging system to auto-sense the optimal battery charging performance based on battery levels. Charging will be either constant current, constant voltage, or floating for optimal battery performance.

Cold Start Capable
Turn on the UPS even without utility power as long as there is sufficient battery power.

5-inch Touchscreen LCD
Colorful, easy-to-read LCD screen shows real-time status information of your UPS power conditions including the voltages, capacity level, battery level, faults, event logs, settings, and more.

Intelligent Slot
For use with a network management card to remotely monitor and control the UPS from a web browser.

Power Management Software
Monitor and control the UPS from your computer with the included user-friendly software to automate computer shutdown, monitor battery levels, set UPS parameters, receive alerts of abnormalities, and more.

Optional Accessories (Not Included)
• Network Management Card - For remote power monitoring. See model number #SNMP3-2 for compatibility with this UPS series.
• Parallel Cable - Parallel up to 6 x ULT-P20K33HV for parallel redundancy. 1 x parallel cable required per UPS set.

Warranty
1-year equipment warranty and 1-year battery warranty. See Terms and Conditions, and Warranty Policy pages for additional information.
OVERVIEW
Model ULT-P20K33HV
Capacity 20kVA / 20kW (20000VA / 20000W)
Phase 3-phase in / 3-phase out
Topology Online double-conversion
INPUT
Voltage & Configuration 3 x 208/360Vac Wye
(3Ph + N + G)
3 x 220/380Vac Wye
(3Ph + N + G)
3 x 230/400Vac Wye
(3Ph + N + G)
3 x 240/415Vac Wye
(3Ph + N + G)
Voltage Range -30% up to +20%
Frequency (Synchronized Range) 50 / 60Hz +/- 4Hz
Frequency (Battery Mode) 50 / 60Hz +/- 1Hz
Power Factor >0.99 at 100% load
THDi <3% at linear load / <5% at non-linear load
Inlet Hardwire terminal
OUTPUT
Voltage & Configuration 3 x 208/360Vac Wye
(3Ph + N + G)
(Derates to 90% if output set to 3 x 360Vac)
3 x 220/380Vac Wye
(3Ph + N + G)
3 x 230/400Vac Wye
(3Ph + N + G)
3 x 240/415Vac Wye
(3Ph + N + G)
Frequency Range
(Synchronized Range)
50Hz: 46 - 54Hz
60Hz: 56 - 64Hz
Frequency Range (Battery Mode) 50 / 60Hz +/- 0.5Hz
Voltage Regulation <1%
Voltage Balance  
Current Crest Ratio 3:1 (max.)
THDv for Linear-Load <1% at linear load
<3% at non-linear load
Transient Reponse  
Transient Recovery Time  
Phase Displacement  
Power Factor 1.0
Overload Threshold Line Mode: 110%: up to 60 minutes; 125%: up to 10 minutes; 150%: up to 1 minute; >150%: immediate shutdown
Battery Mode: 110%: up to 30 seconds; 130%: up to 10 seconds; >130%: up to 1 second
Wave Form (Battery Mode) Sine wave
Outlet Hardwire terminal
TRANSFER TIME
Line To/From Battery 0ms
Inverter To/From Bypass 0ms
(<4ms interruption from inverter to bypass if phase lock fails)
EFFICIENCY
Line Mode 96% at full load with batteries fully charged
Battery Mode  96%
ECO Mode 99% at full load with batteries fully charged
BATTERY
Chemistry Sealed lead-acid
Quantity & Size (16 x 16) x 12V / 9Ah x 1 string (total 32 pieces)
Recharge Time 9 hours to 90% capacity
Charging Current 1A - 12A (adjustable)
Floating Battery Voltage +/- 218.5V +/-10%
PROTECTION
Emergency Power Off (EPO) Yes
Overload Protection Yes
Overcharge Protection Yes
Surge Suppression Yes
EMI / RFI Filter Yes, full time
ADDITIONAL FEATURES
MBS Yes, built-in maintenance bypass switch to safely route electricity during maintenance and servicing
ECO Mode Yes
External Battery Connector No, must purchase ULT-P20KL33HV (extended runtime model) for this feature
Parallel Units Yes, up to 6 units can be set up in parallel
COMMUNICATION
USB Port Yes, for power management software to control and monitor the UPS conditions
RS232 Port Yes, for firmware updates only
Software Compatible with Windows 10/8/7, Server 2012 R2 / 2008 R2, Linux 32-Bit / 64-Bit, Sun Solaris, IBM Aix, Compaq True64, SGIIRIX, FreeBSD, HP-UX, mac
Intelligent Slot Yes, for SNMP3-2 card (not included) for remote power management
STATUS INDICATORS
LCD Screen Yes, 5-inch screen shows Input/Output Voltages, Battery Level, Load Level, Fault, status codes, event logs, settings, and more
Audible Alert Yes
WARRANTY
Warranty 1-Year: Equipment and Battery Warranty. See the Terms and Conditions and Warranty Policy pages for additional information.
ENVIRONMENT
Installation Location For indoor, temperature-controlled location free of contaminants only
Cooling Forced air
Operating Temperature 0°C up to +40°C / +32°F up to +104°F
Operating Humidity <95% non-condensing
Noise <60dB at 1 meter
Operating Altitude <1000 meters
(Note: Output power derates at 1% per 100 meters when installed or used in locations with altitude above 1000 meter)
PHYSICAL
Color Black
Form Factor Tower
Product Dimensions (DWH) 630 x 250 x 826 mm / 24.8 x 9.8 x 32.5 in
Product Weight 139 kg / 306.5 lb

 

Product specifications are subject to change without further notice. Maruson assumes no responsibility, and disclaims all liability, for any damages that may result from the use of this information or for any errors or omissions. Battery backup time varies with equipment, configuration, battery age, temperature, etc.

Brochure
Download here.

User Manual
Download here.

Software
Download here.

You must connect the USB from your UPS to your computer to use the software.

Compatible Operating Systems
Windows OS: Windows 10/ Windows 8/ Windows 7/ Windows Server 2016/ Windows Server 2012/ Windows Server 2012 R2/ Windows Server 2008/ Windows Server 2008 R2
mac OS: Mac OS 10.6/ 10.7/ 10.8/ 10.9/ 10.10/ 10.11
Linux 32-Bit and 64-Bit: Fedora 7/Redhat Enterprise 7.5/Centos 7/Open SUSE 11.4/Debian 7/Ubuntu 18.10
Virtual Machines (Agent and Client): VMware ESX/ESXi 6.5