3000VA Online UPS 6 Outlets + Terminal, TAC-LV3K

In stock
SKU
TAC-LV3K
$1,257.00

 

 

Capacity: 3000VA / 2700W
Topology: Online double-conversion
Wave Form: Sine wave
Outlets: 6 + terminal

Features:
• Sine wave output
• DSP technology
• Active PFC
• 0.9 power factor
• Wide input voltage range (55-150Vac)
• 1% output voltage regulation
• Load segment control
• Intelligent slot for an optional network card
• ECO Mode
• Optional external battery bank

TUV logo

The Tacoma is a robust true double-conversion online UPS with pure sine wave output for a reliable, top-of-the-line battery backup solution with power protection for mission-critical equipment that are vulnerable to power fluctuations and outages. DSP-controlled technology provides advanced UPS management and monitoring capabilities while ABM monitors and optimizes battery charging to prolong the lifespan of the UPS and internal batteries. The wide input voltage range improves the reliability of the UPS while the 1% output voltage regulation delivers a more precise output voltage to connected devices. Have peace of mind knowing your mission-critical equipment is protected with uninterrupted performance and enhanced power protection.

 

Typical Applications
Mid-size servers
ATMs
Lab equipment

Networking devices
Surveillance systems
VoIP / PBX systems

Security systems
Gaming computers
Slot machines

 

Main Features
(6) Battery-Backed Outlets + (1) Terminal with Surge Protection
These outlets keep critical electronics online during a temporary blackout, adjust minor voltage fluctuations, and offer protection from power surges and voltage spikes. If a blackout occurs or a power disruption beyond the tolerance range is detected, the UPS will switch over to battery power and supply these outlets with power.

True Double-Conversion Online Topology
The main supply is fed directly into the UPS and charges batteries within the UPS. The battery power is then converted back to the main power to feed the protected equipment.

Zero Transfer Time
True online double-conversion topology for zero transfer time from Line Mode to Battery Mode in case of a power disturbance prevents malfunction of mission-critical equipment.

Pure Sine Wave Output
Best waveform for sensitive electronics. Benefits include:
• Smoother waveform
• Best for sensitive equipment
• Higher quality than a modified sine wave
• Maintains voltage at a safe level
• Motors run at their intended speed and with less heat
• Equipment runs with less noise
• IT equipment lasts longer
• Low harmonic distortion

DSP Controlled Technology
DSP (digital signal processor) controlled technology for high reliability, accuracy, and efficiency.

Active PFC to Improve Power Factor
Active PFC (power factor correction) improves the power factor and power quality of the UPS by reducing harmonic distortion on the electrical system to improve energy efficiency and reduce energy loss. Additional benefits include active wave shaping of input current, low voltage drop, filtering high frequency switching, waveform control through feedback sensing from the power source, and regulation of output voltage based on feedback control.

1% Output Voltage Regulation
The UPS regulates the output voltage to be within 1% of the set output voltage. Voltages outside acceptable ranges can cause electronics and electrical components to overheat and may cause premature failure of the devices.

The voltage reference of this UPS is set to a fixed 1% output voltage regulation even when parameters such as ambient temperature change. A precise output voltage is important for sensitive electronic equipment such as ones that require calibration for accuracy and also sensitive electronics are more susceptible to damage when receiving power outside its input range.

Wide Input Voltage Range
Minimizes the need to switch over to battery power and frequency of battery charge and recharge cycles by correcting extreme voltage distortion for higher system reliability.

EMI / RFI Filter
EMI / RFI filter suppresses electromagnetic noise and radio frequency interference transmitted from AC power.

Advanced Battery Management
Maximize battery performance and lifespan with an intelligent, multi-stage battery charging system to auto-sense the optimal battery charging performance based on battery levels.

Overload Protection
Protects the UPS from an overload. If the circuit breaker trips, unplug a few electronics before resetting the circuit breaker and turning your unit back on.

Load Segment Control
Control grouped outlets allows better management of battery power by prioritizing mission-critical devices by manual or pre-setting. This allows mission-critical devices to have longer backup time than non-mission-critical devices.

Set Output Voltage and Frequency (for Battery Mode)
The output voltage can be set to 100 / 110 / 115 / 120Vac and the frequency can be set to either 50Hz or 60Hz for better performance with sensitive electronics when the UPS runs on battery power. In Line Mode or ECO Mode, the UPS output voltage and frequency synchronize with the input voltage and frequency.

NOTE: Setting the UPS output to 50Hz will derate the UPS capacity by 40%. For this UPS, the capacity will be cut down to 1620W maximum output capacity.

Cold Start Capable
Turn on the UPS even without utility power as long as there is sufficient battery power.

Auto-Restart During AC Recovery
Once power returns to normal and the battery levels are sufficient, the UPS will automatically restart.

Off-Mode Charging
The UPS continues charging the internal batteries when powered off as long as the unit is plugged into an AC mains wall socket.

Power Management Software
Monitor and control the UPS from your computer with the included user-friendly software to automate computer shutdown, monitor battery levels, set UPS parameters, receive alerts of abnormalities, and more.

LCD Screen
See real-time status information of your UPS power conditions including the voltages, battery level, fault detected, and more.

Emergency Power Off (EPO) Tab
Instantly shut off the UPS and prevent the UPS from supplying power in the event of an emergency.

Mute Audible Alarm
Temporarily mute the audible alarm from you UPS by pressing the ON button when audible alerts are ongoing. The mute setting is reset once the UPS returns to a normal state for the next time unusual activity is detected.

Optional Accessories (Not Included)
• Network Management Card - For remote power monitoring. See model number #NMC for compatibility with this UPS series.
• Add-On External Battery Banks - Extend the battery runtime in the event of an extended power outage. See model # TAC-LV3KBB for compatibility with this UPS series. Maximum 3 x TAC-LV3BB may be used.

Warranty (US & Canada)
2-year equipment warranty, 2-year battery warranty, and 2-year $25,000 connected equipment warranty with product registration. See Terms of Use and Warranty pages for additional information.



WARNING: The batteries, battery posts, terminals, and related accessories can expose you to chemicals including lead and lead compounds, which are known to the State of California to cause cancer and birth defects, or other reproductive harm. Wash hands after handling. For more information, go to www.p65warnings.ca.gov.
OVERVIEW
Model TAC-LV3K
Capacity 3000VA / 2700W
Topology Online double-conversion
INPUT
Voltage 100 / 110 / 115 / 120 Vac
Voltage Range 55 - 150Vac
Frequency 50 / 60Hz (auto-sensing)
Inlet NEMA L5-30P, 30A locking plug
OUTPUT
Output Voltage 100 / 110 / 115 / 120 Vac
Frequency Range (on Battery) 50 / 60 Hz +/- 1%
Voltage Regulation <1%
THDv for Linear-Load 4%
THDv for Non-Linear-Load 8%
Crest Factor 3:1
Wave Form (on Battery) Sine wave
Outlet 4 x NEMA 5-15R; 2 x NEMA 5-15/20R; 1 x hardwire terminal
TRANSFER TIME
Line To/From Battery 0ms
Inverter To/From Bypass <4ms
ECO to Battery <10ms
EFFICIENCY
Line Mode >89%
Battery Mode >86%
ECO Mode >95% at full load with batteries fully charged
BATTERY
Chemistry Sealed lead-acid
Quantity & Size 6 x 12V / 9Ah
Recharge Time 5 hours to 90% capacity (internal batteries only)
PROTECTION
Emergency Power Off (EPO) Yes
Overload Protection Yes
Overcharge Protection Yes
Network / Phone / Fax Surge Suppression Yes, RJ-11/45 combo ports (1-in, 1-out)
Surge Suppression Yes
EMI / RFI Filter Yes, full time
ADDITIONAL FEATURES
Programmable Outlets Yes
ECO Mode Yes
External Battery Connector Yes, maximum 4 external battery banks (TAC-LV2BB)
COMMUNICATION
USB Port Yes, for power management software to control and monitor the UPS conditions
RS232 Port Yes, for power management software to control and monitor the UPS conditions
Software Compatible with Windows 10/8/7/ Server 2012 R2 / 2008 R2 / Linux 32-Bit / 64-Bit / mac 10.6 to 10.11
Intelligent Slot Yes
STATUS INDICATORS
LCD Screen Yes, for Input/Output Voltages, Battery Level, Fault, and more
Audible Alert Yes
WARRANTY
Warranty 2-Year: Equipment and $25,000 Connected Equipment Warranties. 2-Year: Battery Warranty. See Terms of Use and Warranty pages for additional information.
PHYSICAL
Color Black
Form Factor Tower
Product Dimensions (DWH) 14.9 x 7.4 x 12.4 in / 383 x 190 x 318 mm
Product Weight 59.5 lb / 27 kg

 

Product specifications are subject to change without further notice. Maruson assumes no responsibility, and disclaims all liability, for any damages that may result from the use of this information or for any errors or omissions. Battery backup time varies with equipment, configuration, battery age, temperature, etc.

Connect up to 3 external battery banks for extended runtime. Do not exceed 3 EBBs.

TAC-LV3K Runtime
340W 62 minutes   1700W 8.5 minutes
675W 27.5 minutes   2025W 6 minutes
1020W 19.5 minutes   2400W 4.5 minutes
1350W 11 minutes   2700W 3 minutes

 

TAC-LV3K + 1EBB Runtime
340W 190 minutes   1700W 27 minutes
675W 85 minutes   2025W 19 minutes
1020W 60 minutes   2400W 14 minutes
1350W 35 minutes   2700W 9.5 minutes

 

TAC-LV3K + 2EBB Runtime
340W 320 minutes   1700W 45 minutes
675W 140 minutes   2025W 32 minutes
1020W 103 minutes   2400W 24 minutes
1350W 57 minutes   2700W 16 minutes

TIME (Minutes)
LOAD (WATTS)

Brochure
Download here.

User Manual
Download here.

Software
Download here.

You must connect the USB from your UPS to your computer to use the software.

Compatible Operating Systems
Windows OS: Windows 10/ Windows 8/ Windows 7/ Windows Server 2016/ Windows Server 2012/ Windows Server 2012 R2/ Windows Server 2008/ Windows Server 2008 R2
mac OS: Mac OS 10.6/ 10.7/ 10.8/ 10.9/ 10.10/ 10.11
Linux 32-Bit and 64-Bit: Fedora 7/Redhat Enterprise 7.5/Centos 7/Open SUSE 11.4/Debian 7/Ubuntu 18.10
Virtual Machines (Agent and Client): VMware ESX/ESXi 6.5

My serial number for the software does not work
The serial number to use the included software is printed on your CD; it is not the serial number of your UPS unit.

 

Change From Standby Mode to Line Mode
In Standby Mode, the outlets are not supplying power to connected equipment. Change the UPS from Standby Mode to Line Mode for connected equipment to receive power by pressing the ON button while in Standby Mode for two seconds. The UPS will take approximately 15 seconds to complete startup diagnostics before switching to Line Mode.

Note: The ON button and OFF button are not the same buttons. The ON button is the far left button and the OFF button is the second button from the left.

 

Setting the Output Voltage and Frequency (for Battery Mode)
Setting the UPS output voltage and frequency is only for when the UPS is in Battery Mode. This UPS does not offer frequency converter mode. During normal operations, the output voltage and input frequency mimic the input voltage and input frequency with adjustments to keep the output voltage and output frequency within the tolerance range.

LET'S CHAT

Not sure which model to purchase? Or, need help with a purchased item? Let us know how we can help.

PRODUCT REGISTRATION

Register your product for warranty coverage and expediated service requests.

WARRANTY

Find additional information on our warranty policy.