20kVA 208/220V 3-Phase Wye Modular Online UPS System, MAT-VX20KLVSYS
Capacity: 20000VA / 18000W (20kVA / 18kW)
Topology: Online double-conversion
Wave Form: Sine wave
Voltage & Configuration: 120/208V or 127/220V 3-phase Wye
Features:
• 20KVA power module (max. 60KVA capacity per cabinet)
• DSP controlled technology and high-frequency design for optimal performance
• 92.5% high efficiency rating in Line Mode
• 1.0 high output power factor
• Low MTTR (mean time to repair) simplifies maintenance and replacement
• Fast charging current up to 8A per power module
• Built-in maintenance bypass switch
• High overload threshold: 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
• 5.6-inch LCD with comprehensive system conditions
The Matrix VX 33 is a modular 3-phase Wye double-conversion online UPS designed to scale with your organization as it grows and ensure continued operation during critical power disturbances. A high-density, space-saving design with DSP-controlled technology, this UPS delivers a highly reliable system with low harmonic distortion, low total cost of ownership (TCO), and minimal downtime for repair or maintenance (MTTR) with MBS and hot-swappable power module functions. Use up to three 20kW power modules for up to 60kW capacity system, or as 1+1 or N+1 configuration for enhanced system reliability in case one module fails. With an efficiency of 92.5%, over 0.99 power factor, and an output voltage regulation of less than 1%, this UPS offers less power loss and reduces energy consumption to connected loads while providing precise output voltage for optimal performance of connected loads. The front-facing system and plug-and-play power module system was specially designed to simplify maintenance and replacement, and additional benefit of decreasing servicing time and costs. Advanced monitoring tools offers comprehensive status information in real-time or look up historical events from the event log. This is a sophisticated solution for organizations looking to protect mission-critical equipment while enabling scaling and expansion of infrastructure without compromising on reliability. |
Protects From Brief blackouts Power sag Power surge |
Undervoltage Overvoltage Line noise |
Frequency variation Switching transient Harmonic distortion |
Typical Applications Server rooms Surveillance center |
Commercial equipment Networking equipment |
Telecom equipment Small / mid-size data center |
Main Features High Efficiency in Online Double-Conversion Topology 92.5% Line Mode efficiency reduces the overall total cost of ownership with the reliability of online double-conversion topology. The power factor >0.99 means less power loss for better performance and power efficiency to connected loads. DSP Controlled Technology DSP (digital signal processor) controlled technology for high reliability, accuracy, and efficiency. Modular Design for Scalability The modularization design of this series was made with flexibility to expand the power system and backup time as demand changes in the future. Each UPS cabinet holds up to three 20KW power modules for total 60KW capacity. If one power module fails, the other two power modules automatically take over to continue supplying power to mission critical equipment. The front-facing trays, control panels, and connectors allow for easy access during installation, maintenance, and repair. Output Voltage Regulation <1% The UPS regulates the output voltage to be within 1% of the set output voltage. Voltages outside acceptable ranges can cause electronics and electrical components to overheat and may cause premature failure of the devices. A precise output voltage is important for sensitive electronic equipment such as ones that require calibration for accuracy and also sensitive electronics are more susceptible to damage when receiving power outside its input range. High Overload Threshold Threshold Keeps the UPS running in Line Mode when overloaded for a period time. This series will keep running in Line Mode up to 60 minutes at 110% overload capacity and up to 1 minute at 130% overload capacity. Low MTTR (Mean Time to Repair) and Hot Swappable Modules The modular design simplifies and expediates replacement, maintenance, and repair of the UPS modules without shutting off the UPS is convenient and cuts down on servicing costs and any lost revenue from being offline. 2A to 8A Battery Charger Select the battery charger up to 8A based on the number of battery banks connected to the UPS for faster recharge times. EMI / RFI Filter EMI / RFI filter suppresses electromagnetic noise and radio frequency interference transmitted from AC power. |
Emergency Power Off (EPO) Tab Instantly shut off the UPS and prevent the UPS from supplying power in the event of an emergency. Compact Design Space-saving design with high performance capabilities with flexibility to expand in size as business needs increase. Maintenance Bypass Switch (MBS) Safely service the UPS while keeping connected equipment powered for zero downtime with the built-in MBS. Expandable Battery Runtime Add up to 4 external battery banks to extend the battery runtime of your UPS. Cold Start Capable Turn on the UPS even without utility power as long as there is sufficient battery power. 5.6-inch LCD with Comprehensive System Conditions A 5.6-inch graphic LCD screen shows real-time status information of the UPS power conditions including the voltages, capacity, battery, faults, event logs, settings, and more, while the intuitive design provides comprehensive system information and setting of the UPS conditions from the display. Intelligent Slot For use with a network management card to remotely monitor and control the UPS from a web browser. Power Management Software RS232 and USB ports connect directly between UPS and computer to control and monitor the software. Add an optional SNMP card for remote power management. Optional Accessories (Not Included) • Add-on Power Module - Additional 20KVA power module to expand overall UPS system capacity, see model # MAT-VX20KLV • Add-on External Battery Cabinet - See model # EBC-VXNB for the battery cabinet. • Network Management Card - For remote power monitoring. See model number #SNMP3-2 for compatibility with this UPS series. Warranty 1-year equipment warranty and 1-year battery warranty. See Terms and Conditions, and Warranty Policy pages for additional information. |
WARNING: The batteries, battery posts, terminals, and related accessories can expose you to chemicals including lead and lead compounds, which are known to the State of California to cause cancer and birth defects, or other reproductive harm. Wash hands after handling. For more information, go to www.p65warnings.ca.gov. |
OVERVIEW | |||
Model | MAT-VX20KLSYS | ||
Capacity | 20kVA / 18kW (20000VA / 18000W) | ||
Cabinet Capacity | 3 slots (add up to 3 x 20kVA modules) | ||
Phase | 3-phase in / 3-phase out | ||
Topology | Online double-conversion | ||
INPUT | |||
Voltage & Configuration | 3 x 120/208Vac Wye (3Ph + N + G) | 3 x 127/220Vac Wye (3Ph + N + G) | |
Voltage Range | 121 - 253 at < 70% load 156 - 253Vac at 100% load |
||
Frequency | 50 / 60Hz (auto sensing) | ||
Frequency | 50 / 60Hz (auto sensing) | ||
Power Factor | >0.99 at 100% load | ||
THDi | <3% at 100% load | ||
OUTPUT | |||
Voltage & Configuration | 3 x 120/208Vac Wye (3Ph + N + G) | 3 x 127/220Vac Wye (3Ph + N + G) | |
Frequency Range (Synchronized Range) |
50Hz: 46 - 54Hz 60Hz: 56 - 64Hz |
||
Voltage Regulation (Steady State) | < +/- 1% typical (balanced load); < +/- 2% (unbalanced load) | ||
Voltage Regulation (Transient) | < +/- 5% typical | ||
Voltage Balance | |||
THDv for Linear-Load | <2% at linear load <4% at non-linear load |
||
Transient Reponse | |||
Transient Recovery Time | |||
Phase Displacement | |||
Power Factor | > 0.99 at 100% load; 0.98 at 50% load | ||
Overload Threshold | Line Mode: 110%: up to 60 minutes; 125%: up to 10 minutes; 150%: up to 1 minute: > 150%: up to 200ms | ||
Wave Form (Battery Mode) | Sine wave | ||
TRANSFER TIME | |||
Line To/From Battery | 0ms | ||
Inverter To/From Bypass | < 20ms | ||
EFFICIENCY | |||
Line Mode | Up to 92.5% at full load with batteries fully charged | ||
Battery Mode | 92.5% | ||
ECO Mode | 97% at full load with batteries fully charged | ||
BATTERY | |||
Quantity & Size | 12V / 9Ah x 20 pieces x 6 strings (total 120 pieces) | ||
Nominal Batteries Voltage | 120Vdc | ||
Float Charging Voltage | 2.25V / cell | ||
Boost Charging Voltage | 2.35V / cell | ||
Temperature Compensation | Yes | ||
Charging Current | 2A to 8A (adjustable) | ||
PROTECTION | |||
Emergency Power Off (EPO) | Yes | ||
Overload Protection | Yes | ||
Overcharge Protection | Yes | ||
Surge Suppression | Yes | ||
EMI / RFI Filter | Yes, full time | ||
ADDITIONAL FEATURES | |||
MBS | Yes, built-in maintenance bypass switch to safely route electricity during maintenance and servicing | ||
Parallel Option | Yes, up to 2 additional for N+2 or N configuration | ||
ECO Mode | Yes | ||
Temperature Sensor | Yes, with add-on Temperature Sensor | ||
COMMUNICATION | |||
USB Port | Yes, for power management software to control and monitor the UPS conditions | ||
RS232 Port | Yes, for firmware updates only | ||
Software | Compatible with Windows 10/8/7, Server 2012 R2 / 2008 R2, Linux 32-Bit / 64-Bit, Sun Solaris, IBM Aix, Compaq True64, SGIIRIX, FreeBSD, HP-UX, mac | ||
Intelligent Slot | Yes, for SNMP3-2 card (not included) for remote power management | ||
STATUS INDICATORS | |||
LCD Screen | Yes, 5.7-inch screen shows Input/Output Voltages, Battery Level, Load Level, Fault, configuration, status codes, event logs, settings, and more | ||
Audible Alert | Yes | ||
WARRANTY | |||
Warranty | 1-Year: Equipment and Battery Warranty. See the Terms & Conditions, and Warranty Policy pages for additional information. | ||
ENVIRONMENT | |||
Installation Location | For indoor, temperature-controlled location free of contaminants only | ||
Cooling | Built-in fan | ||
Operating Temperature | 0°C up to +40°C / +32°F up to +104°F (Note: Output capacity derates to 90% at 35°C / 95°F and 80% at 40°C / 104°F) |
||
Operating Humidity | <95% non-condensing | ||
Noise | <68.2dB at 1 meter | ||
Operating Altitude | <1000 meters (Note: Do not operate in locations above 1000 meters from sea level) |
||
PHYSICAL | |||
Color | Black | ||
Steering Casters | Yes | ||
Leveler Legs | Yes, for stability at installation location | ||
Rack Height | 30U (UPS Cabinet: 15U; Battery Cabinet: 15U) |
||
Dimensions (DWH) | 1000 x 515 x 1415 mm / 20.3 x 39.4 x 55.7 in (UPS Cabinet: 1000 x 515 x 760 mm / 20.3 x 39.4 x 29.9 in; Battery Cabinet (without wheels): 1000 x 514 x 655 mm / 20.3 x 39.4 x 25.8 in) |
||
Weight | 616 kg / 1358.05 lbs (20KVA Power Module: 34 kg / 75 lb; UPS Cabinet: 195 kg / 430 lb; Battery Cabinet (with batteries): 387 kg / 853.3 lb) |
Product specifications are subject to change without further notice. Maruson assumes no responsibility, and disclaims all liability, for any damages that may result from the use of this information or for any errors or omissions. Battery backup time varies with equipment, configuration, battery age, temperature, etc. |
Brochure
Download here.
User Manual
Download here.
Software
Download here.
You must connect the USB from your UPS to your computer to use the software.
Compatible Operating Systems
Windows OS: Windows 10/ Windows 8/ Windows 7/ Windows Server 2016/ Windows Server 2012/ Windows Server 2012 R2/ Windows Server 2008/ Windows Server 2008 R2
mac OS: Mac OS 10.6/ 10.7/ 10.8/ 10.9/ 10.10/ 10.11
Linux 32-Bit and 64-Bit: Fedora 7/Redhat Enterprise 7.5/Centos 7/Open SUSE 11.4/Debian 7/Ubuntu 18.10
Virtual Machines (Agent and Client): VMware ESX/ESXi 6.5